Key product
AC Input
Input rating100 VAC to 240 VAC, 50 Hz/60 Hz, 6 A to 3 AOperating voltage range1

90 VAC to 264 VAC

Nominal input frequency

50 Hz/60 Hz

Operating frequency range1

47 Hz to 63 Hz

Efficiency

78% typical

Over-current protection

Internal fuse in line

Main power disconnect

The AC power cable provides main power disconnect. Do not position the equipment so that it is difficult to disconnect the power cord. The front-panel power switch causes the internal chassis power supply to provide DC power to the PXI Express backplane.

Chassis Cooling
Module cooling

Forced air circulation (positive pressurization) through one 150 CFM fan

Module slot airflow direction

Bottom of module to top of module

Module intake

Bottom of chassis

Module exhaust

Top, right side of chassis

Slot cooling capacity

58 W; slot 6 supports 58 W cooling with high fan mode

Operating Environment
Ambient temperature range
When all peripheral modules require ≤38 W cooling capacity per slot

0 °C to 50 °C (IEC 60068-2-1 and IEC 60068-2-2.)2 Meets MIL-PRF-28800F Class 3 low temperature limit and high temperature limit.

When any peripheral module requires >38 W cooling capacity per slot

0 °C to 40 °C (IEC 60068-2-1 and IEC 60068-2-2.)2 Meets MIL-PRF-28800F Class 3 low temperature limit and MIL-PRF-28800F Class 4 high temperature limit.

Relative humidity range

20% to 80%, noncondensing

Reviews

There are no reviews yet.

Be the first to review “NI PXIe-1083,5-Slot (5 Hybrid Slots), Up to 2 GB/s PXI Chassis (787026-01)”

Your email address will not be published. Required fields are marked *